Clean-Rooms

All Climate Mechanical has designed, installed and serviced HVAC systems for clean-rooms. We do not install your clean-room structures we leave that to the clean-room manufacturer. We install, repair and maintain the cooling, humidifying, static pressure and exhaust systems to ensure a consistent, reliable environment for your R&D or products.

We have worked with soft wall and hard wall clean-rooms, RO and DI water systems, Desiccant dehumidifiers, electric humidifiers, ultrasonic humidifiers, Pneumatic and DDC controls.

What class clean room do you need?

Class limits (maximum allowable particles)

ISO FED STD 209 0.1 µm 0.2 µm 0.3 µm 0.5 µm 5.0 µm
CLASS 3 1 1000 / 35 35 / 1
CLASS 4 10 10,000 / 345 75 30 352 / 10 0
CLASS 5 100 100,000 / 3,450 750 300 3520 / 100 0
CLASS 6 1,000 1,000,000 / 34,50 N/A N/A 35,200 / 1,000 7
CLASS 7 10,000 345,000 N/A N/A 352,000 / 10,000 70
CLASS 8 100,000 3,450,00 N/A N/A 3,520,000 / 100,000 700

ISO 14644-1 (per cubic meter)
Fed Std. 209 E USA (per cubic foot)
ISO standard requires results to be shown in cubic meters (1 cubic meter = 35.314 cubic feet)

Class 1

  • 540 to 600+ air changes per hour (98%+ ceiling coverage)
  • ULPA filters (99.9995% on .12 microns)
  • Gel/Flush grid ceiling systems with raised floors are required
  • Outside/makeup air to be pre-filtered with a HEPA filterClass 10
  • 540 to 600 air changes per hour (85-90% ceiling coverage)
  • 99.999% on 0.3 microns, with a raised floors
  • 90%+ coverage with low wall returns
  • Gasket grids with negative plenums acceptable
  • HEPA filters on makeup airClass 100
  • 400 to 480 air changes per hour (60-80% ceiling coverage)
  • 99.99% HEPA filters
  • Raised floor assures optimal performance. Low wall returns work when they are no further than 12′ from the center of the room¹
  • Gasket ceiling gridClass 1,000
  • 120 to 150 air changes per hour (40-50% ceiling coverage)
  • 99.99% HEPA filter
  • Gasket ceiling grid
  • Raised floor delivers best performance, but low wall returns are very common¹Class 10,000
  • 45 to 60 air changes per hour (10-20% ceiling coverage)
  • 99.97% or 99.99% HEPAs
  • Low wall or ceiling returns acceptable in most applications¹Class 100,000
  • 20 to 30 air changes per hour (5% ceiling coverage)
  • HEPA filters or 95% HEPAs (95%+ ASHRAE box filters²) located downstream of the HVAC unit
  • Heat load may require more air changesFor more information about how All Climate can help you with your clean-room or mechanical need please feel free to contact us.